Copyright © D 361 - 03/091 of 20- Data BrochureMixing Control 361D 36103/09The Mixing Control 361 is designed to control the supply water temperature
Copyright © D 361 - 03/09 10 of 20InstallationCAUTIONImproper installation and operation of this control could result in damage to the equipment and p
Copyright © D 361 - 03/0911 of 20Output Connections System Pump Contact (Sys Pmp)The Sys Pmp output terminal (5) on the 361 is a powered output.When t
Copyright © D 361 - 03/09 12 of 20Indoor SensorIf an indoor sensor is used, connect the two wires from the sensorto the Com and Indr terminals (15 and
Copyright © D 361 - 03/0913 of 20Test The Outputs System Pump (Sys Pmp)If a system pump is connected to the Sys Pmp terminal (5), makesure that power
Copyright © D 361 - 03/09 14 of 20DIP Switch SettingsThe DIP Switch settings on the control are very important and should beset to the appropriate set
Copyright © D 361 - 03/0915 of 20Press and release the Item button to advance to the units adjustment. Use the or button to set the scaleto °F or °
Copyright © D 361 - 03/09 16 of 20Adjust Menu (1 of 2)The type of terminal units that are being used in theheating system.(OUTDR DSGN ≠ OFF)1 (High Ma
Copyright © D 361 - 03/0917 of 20Testing the ControlThe Mixing Control 361 has a built-in test routine which is used to test themain control functions
Copyright © D 361 - 03/09 18 of 20TroubleshootingWhen troubleshooting any heating system, it is always a good idea to establish a set routine to follo
Copyright © D 361 - 03/0919 of 20The control was unable to read a piece of information from its EEPROM. This error can be caused by anoisy power sourc
Copyright © D 361 - 03/09 2 of 20ItemThe abbreviated name of the selected item will be displayed in the item field of thedisplay. To view the next avai
Limited Warranty The liability of tekmar Control Systems Ltd. and tekmarControl Systems, Inc. (“tekmar”) under this warranty is limited. The purchaser
Copyright © D 361 - 03/093 of 20DisplaySymbol DescriptionVIEWTARGETINDRDSGNDIFFBOILMIXOUTDRROOM WWSDADJUST°F°CMAXMINUNOCCTerminalUnit3010 7050MixingDe
Copyright © D 361 - 03/09 4 of 20Sequence of OperationSection AGeneral OperationPage 4-5Section BMixingPage 5-8Section CBoiler OperationPage 8-9Sectio
Copyright © D 361 - 03/095 of 20EXERCISING The 361 has a built-in exercising function. If a pump has not been operated at least once every 3 days, th
Copyright © D 361 - 03/09 6 of 20CHARACTERIZED HEATING CURVE When used as a mixing reset control, the 361 varies the supply water temperature based on
Copyright © D 361 - 03/097 of 20High Mass Radiant (1) This type of a hydronic radiant floor is embedded in either a thick concrete or gypsumpour. This
Copyright © D 361 - 03/09 8 of 20MIXING MINIMUM (MIX MIN) The MIX MIN is the lowest temperature that the control is allowed to useas a MIX TARGET temp
Copyright © D 361 - 03/099 of 20Section C2: Boiler Sensor PlacementBOILER SENSOR ON THE SUPPLY (Boiler Sensor DIP switch = Supply) The boiler sensor c