9 of 24 © 2007 D 420 - 08/07
Item Field
Range
Access Description
100 to 220°F
(38.0 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
DHW EXCHANGE OCCUPIED
SECTION F
The minimum boiler target temperature to the DHW
heat exchanger during the Occupied period.
Note: This item is only available when DHW Mode
is set 1 through 4.
OFF, ON
Default = OFF
Ad
DHW EXCHANGE UNOCCUPIED SECTION F
Selects whether the control should respond to DHW
demands during the Unoccupied period. This item is
only available when DHW Mode is set 1 through 4
and a network setback schedule is selected.
OFF,
1 (parallel, no priority)
2 (parallel, priority)
3 (pri-sec, no priority)
4 (Pri-sec, priority)
Default = 1
Ad
SETPOINT MODE SECTION H
Selects the Setpoint mode of operation. This
determines the operation of the primary pump.
60 to 220°F
(15.5 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
SETPOINT OCCUPIED SECTION H
The minimum boiler target temperature when a
setpoint demand is present during the Occupied
period.
Note: This item is only available when Setpoint Mode
is set 1 through 4.
OFF, ON
Default = OFF
Ad
SETPOINT UNOCCUPIED SECTION H
Selects whether or not a Setpoint demand will be
responded to during the UnOccupied period.
Note: This item is only available when Setpoint Mode
is set 1 through 4 and a network setback schedule
is selected.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 70°F (21.0°C)
InS
Ad
WWSD OCCUPIED
SECTION B
The system’s warm weather shut down temperature
during the Wake and Occupied periods.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F (15.5°C)
Ad
WWSD UNOCCUPIED SECTION B
The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note: This item is only available when the Schedule
is not set to OFF.
Adjust Menu (3 of 3)
ADJUST MENU
After the last item, the control returns to the first item in the menu.