Section
Advanced
Installer
Display Description Range
Actual
Setting
The maximum supply temperature for the mixing
system.
(OUTDR DSGN OFF)
80 to 225°F
(27 to 107°C)
B3
The location of the boiler sensor. This effects
operation of the boiler contact.
(Boiler sensor is present)
Return, Supply
C2
The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)
OFF, 80 to 180°F
(OFF, 27 to 82°C)
C1
The systems warm weather shut down.
35 to 100°F, OFF
(2 to 38°C, OFF)
B3
The units of measure that all of the temperatures
are to be displayed in the control.
°F, °C
This item exits the ADJUST menu by pressing
either the or
button.
Adjust Menu (2 of 2)
ADJUST
MIX
°
F
MAX
Return Supply
BOIL
ADJUST
ADJUST
WWSD
°
F
ADJUST
BOIL
°
F
MIN
ADJUST
°
F
ADJUST