362 Adjust Menu (2 of 4)
Actual
Setting
The maximum length of morning boost.
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
No RTU Connected
10K ZoIn MODE = 1
0:20 to 8:00 hrs
Default = OFF
0 to 50˚F
(0 to 28˚C)
Default = 15°F (-9°C)
The minimum supply water temperature for the
mixing system.
DIP switch =
Characterized Heating Curve
MODE = 1
OFF, 35 to 150˚F
(OFF, 2 to 66˚C)
Default = OFF
The design indoor air temperature used in the
heat loss calculations for the heating system.
DIP switch =
Characterized Heating Curve
MODE = 1
35 to 100˚F
(2 to 38˚C)
Default = 70°F (21°C)
The starting water temperature used in the Reset
Ratio calculation for the heating system.
DIP switch =
Reset Ratio
MODE = 1
35 to 150˚F
(2 to 66˚C)
Default = 70°F (21°C)
The outdoor starting temperature used in the
reset ratio calculation for the heating system.
DIP switch =
Reset Ratio
MODE = 1
35 to 85˚F
(2 to 29˚C)
Default = 70°F (21°C)
The amount the mixing supply temperature is
reduced when the control is in the
UnOccupied Mode.
DIP switch =
Reset Ratio
DIP switch =
Setback
MODE = 1
The design supply water temperature used in the
heat loss calculation for the heating system.
MODE = 1
70 to 220˚F
(21 to 104˚C)
Default = 120°F (49°C)
The type of terminal units that are being used in
the heating system.
DIP switch =
Characterized Heating Curve
MODE = 1
HRF1 (Heavy), HRF2
(Light), (Fan-) COIL,
CONV (ector), RAD
(iator), BASE (board)
Default = HRF1
The design outdoor air temperature used in the
heat loss calculation for the heating system
MODE = 1
-60 to 32˚F
(-51 to 0˚C)
Default = 10°F (-12°C)
The maximum supply temperature allowed
80 to 210˚F, OFF
(27 to 99˚C, OFF)
Default = 140°F (60°C)
The type of mixing device that is to be used.
FLOT (Floating),
VAR (Variable speed)
Default = VAR
Section
LTD
INST
ADV
Range
Access
Level
DescriptionItem Field
USER
B1
B1
B1
B1
B1
B1
B1
B1
A
B1
A
B1
for the mixing system.