7 of 20 © 2007 D 421 - 08/07
Item Field
Range
Access Description
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
InS
Ad
OUTDOOR DESIGN SECTION B
The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically set
to the temperature of the coldest day of the year.
VAr, FLt
Default = VAr
InS
Ad
MIX MODE
Select the type of mixing device to be used for mixing.
Options are variable speed injection pump (VAr) or
floating action (FLt).
1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 1
InS
Ad
MIX TERMINAL SECTION B
The type of heating terminal units that are being
used in the mix temperature zones.
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
Ad
MIX INDOOR SECTION B
The design indoor air temperature used in the heat
loss calculation for mix zones. Typically set to 70°F
(21.0°C).
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
InS
Ad
MIX DESIGN SECTION B
The supply water temperature required for the mix
temperature zones on the typical coldest day of the
year.
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
Ad
MIX MINIMUM SECTION C
The minimum allowed mix target temperature.
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
Ad
MIX MAXIMUM SECTION C
The maximum allowed mix target temperature.
Adjust Menu (1 of 2)
The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.
Continued on next page.
ADJUST MENU