© 2007 D 421 - 08/07 8 of 20
Item Field
Range
Access Description
30 to 230 seconds
Default = 105
Ad
MIX MOTOR
The time that the actuating motor requires to operate
from fully closed to fully open.
Note: This item is only available when the Mix Mode
setting is set to floating action (FLt).
OFF, 80 to 180°F
(OFF, 26.5 to 82.0°C)
Default = 140°F
(60.0°C)
InS
Ad
BOILER MINIMUM SECTION D
The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.
Au, 2 to 42°F
(Au, 1 to 23.5°C)
Default = Au
Ad
BOILER DIFFERENTIAL SECTION D
The temperature differential that the control is to use
when it is operating the boiler.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tN4 DIP switch is set to Boiler.
Au, 5 to 30 min
Default = Au
Ad
CYCLES PER HOUR
The cycle length that all tN4 device heating zones
will synchronize to.
NONE, Mbr1, Mbr2,
Mbr3, Mbr4
Default = NONE
InS
Ad
SCHEDULE
Selects which network setback schedule the control
will follow.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 70°F (21.0°C)
InS
Ad
WWSD OCCUPIED SECTION B
The system’s warm weather shut down temperature
during the Wake and Occupied periods.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F (15.5°C)
Ad
WWSD UNOCCUPIED
SECTION B
The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note: This item is only available when the Schedule
is not set to OFF.
Adjust Menu (2 of 2)
ADJUST MENU
After the last item, the control returns to the first item in the menu.