- Data Brochure
Boiler Control 264
D 264
12/08
1 of 32 © 2008 D 264 - 12/08
The tekmar Boiler Control 264 can control the supply water temperature from up to 4 on / off stages based on outdoor temperature,
control for Domestic Hot Water (DHW) generation, or a setpoint requirement. A large easy to read display provides current system
temperatures and operating status. The control has outputs for a primary pump and either a combustion air damper or alarm. Based
on the mode of operation selected, the control can operate different combinations of boiler stages and boiler pumps.
Additional functions include:
Installer and Advanced access levels
Primary pump output
Individual boiler pump outputs (in applicable modes)
• Pump exercising
Pump purging (primary and boiler)
0 – 10 V (dc) input signal
Boiler demand for space heating loads
DHW demand for DHW loads
Setpoint demand for setpoint loads
Test sequence to ensure proper component operation
CSA C US certified
Setback input for energy savings
Input
Universal Sensor
Included
Input
Universal Sensor
Included
Input
Outdoor
Sensor
Included
Input
Timer or Switch
Optional
Input
0-10 V (dc)
External Signal
Input
Setpoint / DHW
Demand
Input
115 V (ac)
Power Supply
Input
Boiler
Demand
Output
Primary
Pump
Output
Boiler
Output
Pump
Or
Output
Combustion Air
or Alarm
Or
Output
DHW Pump Or
DHW Valve
M
Or
Or
External Input
Setp/
DHW
UnO
Com
1101
H2027D
Boiler Control 264
Four Stage Boiler & DHW / Setpoint
115 V ±10% 50/60 Hz 600 VA
230 V (ac) 5 A 1/3 hp
20 to 260 V (ac) 2 VA
Ret
Boil
Made in Canada by
tekmar Control Systems Ltd.
tektra 943-02
not testing
testing
red
red
testing paused
Power
Relays
Demands
184321 5
Out
Signal wiring must be rated at least 300 V.
Test
Menu Item
191514 23
Power
N
98
Prim
L
Com
Dem
7
6
Boil
Dem P1SwSup
Boil
Do not apply power
Boiler Demand
DHW / Setpoint Demand
WWSD
22
C.A. /
13
Alarm
12 16 17
DHW
Pmp/Vlv1
Relay
12
Relay
23
Relay
3
Fixed Last
Rotate
Fixed Lead
Exercise
Alarm
Adv
Installer
C.A.
Up to 2 Lo/Hi Boilers
1 Three Stage Boiler & 1 Pump
Modes
1
2
3
4
For maximum
heat, press &
hold Test for 3
seconds.
20 21
4
Relay
4
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
External Input Signal
Offset
Stand Alone
Priority Override
Note:
Boiler, DHW, or
setpoint demand
must be powered
with 20 to 260 V (ac)
before the boiler is
able to fire.
Seitenansicht 0
1 2 3 4 5 6 ... 31 32

Inhaltsverzeichnis

Seite 1 - - Data Brochure

- Data BrochureBoiler Control 264D 26412/08 1 of 32 © 2008 D 264 - 12/08The tekmar Boiler Control 264 can control the supply water temperature f

Seite 2

© 2008 D 264 - 12/08 10 of 32 OUTDOOR DESIGN TEMPERATUREThe outdoor design temperature is the outdoor air temperature that is the typical coldest

Seite 3 - Symbol Description

11 of 32 © 2008 D 264 - 12/08Fancoil (3)A fancoil terminal unit or air handling unit (AHU) consists of a hydronic heating coil and either

Seite 4 - (UNOCCUPIED)

© 2008 D 264 - 12/08 12 of 32 Section E1DHWSection E: Domestic Hot Water Operation Section E1: Domestic Hot Water (DHW)DHW DEMANDA DHW Demand is

Seite 5 - (C. A.)

13 of 32 © 2008 D 264 - 12/08CONDITIONAL DHW PRIORITYThe Conditional DHW Priority Override applies to DHW MODE 2 and 4. If the boiler sup

Seite 6 - Section B1

© 2008 D 264 - 12/08 14 of 32 DHW MODE 2 OPERATIONOn a call for DHW, the control provides DHW priority by shutting off the primary pump (Prim P1)

Seite 7

15 of 32 © 2008 D 264 - 12/087ComDem8Setp/DHW24 to 230 V (ac)Section F1SetpointSection F: Setpoint OperationSection F1: SetpointSetpoint

Seite 8 - Section C1

© 2008 D 264 - 12/08 16 of 32 Section G1External InputSection G: External Input OperationSection G1: External InputEXTERNAL INPUTThe control can

Seite 9 - Section D1

17 of 32 © 2008 D 264 - 12/08External Input Signal Conversion TablesCONVERSION TABLE 0 - 100 - 20 mA*020 - 10 V (dc)01Boiler Target– – –

Seite 10

© 2008 D 264 - 12/08 18 of 32 STEP THREE ———— ROUGH-IN WIRINGAll electrical wiring terminates in the control base wiring chamber. The base has

Seite 11 - Baseboard (6)

19 of 32 © 2008 D 264 - 12/08PrimP11110PowerNL9LN115 V (ac)121324 to 230 V (ac)C.A./AlarmLNMOR1Com2BoilSup3BoilRet4Out2134ComBoilSupBoilR

Seite 12 - Section E1

© 2008 D 264 - 12/08 2 of 32 The control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to

Seite 13

© 2008 D 264 - 12/08 20 of 32 21ComBoilSupBoiler Return SensorIf a boiler return sensor is used, connect the two wires from the Boiler Return Sen

Seite 14 - DHW MODE 4 OPERATION

21 of 32 © 2008 D 264 - 12/08DHW DemandIf a DHW demand is used, measure the voltage between the Setp / DHW and the Com Dem terminals (8 a

Seite 15 - Section F1

© 2008 D 264 - 12/08 22 of 32 9PowerLNPrimP11011LN1514Relay111514Relay1124 to 230 V (ac)LN1312C.A./AlarmM24 to 230 V (ac)LNOR Test The OutputsPri

Seite 16 - Section G1

23 of 32 © 2008 D 264 - 12/08External Input / Stand AloneThe External Input / Stand Alone DIP switch selects whether a tekmar Outdoor Sen

Seite 17 - ——————

© 2008 D 264 - 12/08 24 of 32 Fixed Last / OffThe Fixed Last / Off DIP switch selects whether or not the last boiler is to be included in the rot

Seite 18 - (0 - 10 V dc)

25 of 32 © 2008 D 264 - 12/08View Menu (1 of 1) Outdoor - Current outdoor air temperature as measured by the outdoor sensor.-67 to 149°F

Seite 19

© 2008 D 264 - 12/08 26 of 32 Adjust Menu (1 of 4)Display Description RangeSectionInstallerAdvancedActualSettingD1Room Occupied - The desired roo

Seite 20 - 20 to 260 V (ac)

27 of 32 © 2008 D 264 - 12/08Adjust Menu (2 of 4)Display Description RangeSectionInstallerAdvancedActualSettingD1Terminal Unit - The type

Seite 21 - External Input

© 2008 D 264 - 12/08 28 of 32 Adjust Menu (3 of 4)Display Description RangeSectionInstallerAdvancedActualSettingB1Staging - Selects the firing se

Seite 22

29 of 32 © 2008 D 264 - 12/08Adjust Menu (4 of 4)Display Description RangeSectionInstallerAdvancedActualSettingD1WWSD UnOccupied The syst

Seite 23 - Dip Switch Settings

3 of 32 © 2008 D 264 - 12/08Boiler DemandDHW / Setpoint DemandWWSDPriority OverrideExternal Input SignalOffsetMenu FieldDisplays thecurre

Seite 24 - Off / Exercise

© 2008 D 264 - 12/08 30 of 32 Step 1 The primary pump is turned on and remains on for the entire test routine.Step 2 If the Alarm / C.A. DIP s

Seite 25 - Advanced

31 of 32 © 2008 D 264 - 12/08The control was unable to read a piece of information stored in its memory. Because of this, the control was

Seite 26 - Display Description Range

32 of 32Product design, software and literature are Copyright © 2008 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.All specificatio

Seite 27 - Adjust Menu (2 of 4)

© 2008 D 264 - 12/08 4 of 32 Section AGeneralOperationPage 4 - 6Section BStagingOperationPage 6 - 8Section CPumpOperationPage 8 - 9Section DBoile

Seite 28 - Adjust Menu (3 of 4)

5 of 32 © 2008 D 264 - 12/08COMBUSTION AIR OR ALARM CONTACTThe control has an isolated contact that can be used as either a combustion ai

Seite 29 - Adjust Menu (4 of 4)

© 2008 D 264 - 12/08 6 of 32 EXERCISINGThe control has a built-in exercising feature that is selected through the Exercise / Off DIP switch. To e

Seite 30 - Testing the Control

7 of 32 © 2008 D 264 - 12/08LO / HI OR LO / LOWhen using multi-stage boilers, a selection must be made regarding the staging order of the

Seite 31 - Error Messages

© 2008 D 264 - 12/08 8 of 32 Hi (3)The Hi setting is selected if the boiler(s) that is used has a high thermal mass. This means that the boiler(s

Seite 32 - Technical Data

9 of 32 © 2008 D 264 - 12/08BOILER PUMP OPERATIONIn certain modes of operation, the control can operate the individual boiler pumps on ea