25 of 36 © 2010 D 265 - 07/10
14
12
13
Prim
P1
Power
L
N
N
L
115 V (ac)
16
15
C.A./
Alert
M
24 to 230 V (ac)
or
Low Voltage Alert
Test the Outputs
Primary Pump (Prim P1)
If a primary pump is connected to the Prim P1 term inal (12), make sure that p ower to the
terminal block is off and install a jumper between the Power L and Prim P1 terminals (13
and 12). When power is applied to the Power L and Power N terminals (13 and 14), the
primary pump should start. If the pump does not turn on, check the wiring between the
terminal block and pump and refer to any installation or troubleshooting information
supplied with the pump. If the pump operates properly, disconnect the power and
remove the jumper.
Combustion Air or Alert (C.A. / Alert)
If a combustion air damper or an alert is connected to the C.A. / Alert terminals (15 and 16),
make sure power to the damper or alert circuit is off and install a jumper between
terminals (15 and 16). When the circuit is powered up, the combustion air damper
should open or the alert should activate. If the damper or the alert fails to operate,
check the wiring between the terminals and the damper or the alert and refer to any
installation or troubleshooting information supplied with these devices. If the damper
or the alert operates properly, disconnect the power and remove the jumper.
Boiler 1 and Boiler 2 Contacts
If a boiler is connected to the Boiler 1 and / or Boiler 2 contacts (17 and 18, 19 and
20), make sure power to the boiler circuit(s) is off, and install a jumper between the
terminals. When the boiler circuit is powered up, the boiler should fire. If the boiler does
not turn on, refer to any installation or troubleshooting information supplied with the
boiler. (The boiler may have a flow switch that prevents firing until the primary pump
(Prim P1) or boiler pumps (Boiler Pump 1, 2) are running). If the boiler(s) operates
properly, disconnect the power and remove the jumper.
Boiler 3 / DHW Contact
Boiler Operation
If a boiler is connected to the Boiler 3 / DHW contact (21 and 22), make sure power
to the boiler circuit is off, and install a jumper between the terminals. When the boiler
circuit is powered up, the boiler should fire. If the boiler does not turn on, refer to any
installation or troubleshooting information supplied with the boiler. (The boiler may
have a flow switch that prevents firing until the primary pump (Prim P1) or boiler pump
(Boiler Pump 3) is running). If the boiler operates properly, disconnect the power and
remove the jumper.
DHW Operation
If a DHW pump or DHW valve is connected to the Boiler 3 / DHW contact (21 and 22),
make sure the power to the pump or valve circuit is off and install a jumper between
those terminals. When the DHW circuit is powered up, the DHW pump should turn
on or the DHW valve should open completely. If the DHW pump or valve fails to
operate, check the wiring between the terminals and the pump or valve and refer to
any installation or troubleshooting information supplied with these devices. If the DHW
pump or valve operates correctly, disconnect the power and remove the jumper.
Boiler Pump 1 to Boiler Pump 3 Contacts
If a boiler pump is connected to Boiler Pump 1 contact (23 and 24), make sure that
power to the terminal block is off and install a jumper between the terminals. When
power is applied to circuit, the boiler pump should start. If the pump does not turn on,
check the wiring between the terminal block and pump and refer to any installation
or troubleshooting information supplied with the pump. If the pump operates properly,
disconnect the power and remove the jumper.
Repeat the same procedure for Boiler Pump 2 contacts (25 and 26) and for Boiler Pump 3
contacts (27 and 28) as necessary.
22
21
Boiler 3/
DHW
24 to 230 V (ac)
M
or
L
N
18
17
Boiler
1
1
22
21
Boiler 3/
DHW
Boiler 3
24
23
Boiler
Pump 1
24 to 230 V (ac)
L
N