Tekmar 161 Setpoint Control Installation Bedienungsanleitung Seite 30

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 36
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 29
© 2007 D 161 - 08/07 30 of 36
Error Messages (1 of 4)
Note: Error Messages are only visible while in the Advanced or Installer access level.
Error Message Description
ADJUST ERROR
The setpoint control failed to read the ADJUST menu settings from memory and has reloaded the
factory default settings. Operation stops until the ADJUST menu settings are checked.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the ADJUST menu.
SCENE ERROR
The setpoint control failed to read the SCENE menu settings from memory and has reloaded the
factory default settings. The setpoint control continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the SCENE menu.
SCHEDULE ERROR
The setpoint control failed to read the SCHEDULE menu settings from memory and has reloaded
the factory default settings. The setpoint control continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the SCHEDULE menu.
MISCELLANEOUS ERROR
The setpoint control failed to read the MISCELLANEOUS menu settings from memory and has
reloaded the factory default settings. The setpoint control continues to operate while displaying
this error.
Note: To clear the error, the access level must be set to Advanced before checking all settings in
the MISCELLANEOUS menu.
Seitenansicht 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 36

Kommentare zu diesen Handbüchern

Keine Kommentare